首页 > 分享 > 浅谈消防水池的设计

浅谈消防水池的设计

浅谈消防水池的设计杨思思(江苏省建筑设计研究院有限公司,江苏南京 210019 ) 摘要: 依据《消防给水及消火栓系统技术规范》( GB50974-2014 )的规定,结合具体的工程实例,就建筑地下消防水池的设计及水位确定等问题进行了简要的阐述和分析,以加强消防水源建设,保证消防水池在火灾扑灭过程中能够发挥其应有的作用。关键词: 消防水池水位供水安全 Introduction to the D esign ofF ireP ool Yang Si-si ( Jiang su Provincial Architectural Design & Research Institute Ltd , Jiangsu Nanjing 210019 ) Abstract : According to"T echnical S pecification for F ireW ater and F ireH ydrant S ystem (GB50974-2014) ”, combined with specific engineering example ,t he underground fire pool design was briefly reviewed in this paper . T he problem s such as water level were analy zed , so that we can strengthen the construction of fire water supply, and ensure that fire pool can play its proper role during a fire. Key Words :F ireP ool Water Level Water S upply S ecurity 1 .引言随着当今社会的飞速发展, 为了更加合理的利用土地资源, 高层甚至超高层建筑越来越多的进入到城市的规划及建设中。对于这些建筑, 其防火设计立足于自防自救, 一旦发生火灾, 极易造成重大的人员伤亡及财产损失。根据上海、抚顺、武汉、株州等市火灾统计显示, 扑救失利的火灾案例有 % 是由于缺乏消防用水而导致的[1]。消防水池和消防水泵房是整个建筑消防设施中, 最重要的动力源, 是整个消防供水设施的心脏,在灭火过程中,从消防泵房消防水池内取水,消防水泵将水输送到灭火设备处[2]。作为储存和供给消防用水的构筑物,消防水池是否可靠将直接影响到火灾的扑救效果。 2 .消防水池的设置通常高层建筑消防设计多采取消防水池、屋顶水箱的方式, 超高层建筑则采取消防水池、避难层转输水箱、屋顶水箱的方式供水。《消防给水及消火栓系统技术规范》( GB50974-2014 ) [3] 规定(下文简称《消规》)符合下列情况之一时,应设置消防水池: 1. 当生产、生活用水量达到最大时, 市政给水管网或入户引入管不能满足室内、室外消防给水设计流量; 2. 当采用一路消防供水或只有一条引入管,且室外消火栓设计流量大于 20L/s 或建筑高度大于 50m ; 3. 市政消防给水设计流量小于建筑室内外消防给水设计流量。同时,为了满足发生火灾时的消防总用水量, 《消规》要求消防水池的有效容积由室内外消防系统的设计流量及火灾延续时间

浅谈消防水池的设计 来自淘豆网www.taodocs.com转载请标明出处.

相关知识

浅谈搜救犬的训练和使用
浅谈搜救犬的训练和使用(教学资料)
浅谈动物园笼舍设计
119消防主题文创设计大赛作品征集公告
浅谈趣味动物造型与首饰设计的结合
浅谈宠物用品包装设计的个性化
举报消防不合格的后果
水池的水怎么循环
泰州消防:有奖征集!
不锈钢动物洗澡水槽,宠物洗澡水池,洗澡水池,宠

网址: 浅谈消防水池的设计 https://m.mcbbbk.com/newsview1047143.html

所属分类:萌宠日常
上一篇: 【lanhu海洋馆隧道施工 承接
下一篇: 狗舍如何搭建